SECTION 4 • CONFIGURATION PARAMETERS

DNP Configuration Parameters

These paragraphs describe configuration settings that may be verified/changed from the BE1-851E front

panel or using ASCII protocol commands.

Relay Style Number

BE1-851E relays that support the DNP protocol must have a Style Number that contains the number 3 for

the Com2 RS-485 option. This can be verified by reading the relay Style Number via the front

communication port using the RG-VER ASCII command. (Reference the BE1-851E Instructional Manual,

part number 9289900790).
Example:

>rg-ver

Model Number: BE1-851E

Style Number: H5N1H3N

App Program: VER x.xx.xx xx/xx/xx

Boot Program: VER x.xx

Serial Number:H12345678

BE1-851E Slave Address

BE1-851E relays support DNP through the rear RS-485 communication port, which is communication port

2 (COM2). This port supports Baud Rates: 1200, 2400, 4800, 9600, and 19200, and the default Baud

Rate is 9600.
DNP Slave IED Address Range is from 0 to 65534. Address 65535 (hex FFFF) is used to broadcast

messages to all devices. The communication address can be set by the SG-COM ASCII command. For

more information about changing the relay parameters, refer to the BE1-851E Instructional Manual, part

number 9289900790.
Example: Set the BE1-851E address to be 125, and baud rate to be 9600.
(In the following example, the operator’s commands are in

bold.)

>

a=<global_password> <enter> //enter global password

>ACCESS GRANTED: GLOBAL

>

sg-com2=9600,a125(enter)

>

exit (enter)

>SAVE CHANGES (Y/N/C) ?

>

y <enter>

>CHANGE COMM PARAMETERS

>

To verify port address, enter command

>

sg-com2(enter)

>SG-COM2=9600, A125, P0,R1,X0

9289900792 Rev C

BE1-851E DNP Protocol

4-1