Binary Output Status Points and Control Relay Output Jacks

Table 5-2 lists both the Binary Output Status Points (Object 10) and the Control Relay Output Blocks

(Object 12). It is important to note that Binary Output Status Points are not included in Class 0.

Table 5-2. Binary Output Status Points and Control Relay Output Blocks

Binary Output Status Points:

Object Number: 10

Variations supported: 2

Request Function Codes supported: 1 (read)

Default Variation reported when variation 0 requested: 2 (Binary Output Status)

Control Relay Output Blocks

Object Number: 12

Variations supported: 1

Request Function Codes supported: 3(select), 4(operate), 5(direct operate), 6 (direct operate, noack)

Point

Index

Description

Control Codes And Their Description

0

Hardware Output A State

Latch On: Set Output x to state 1

Latch Off: Set Output x to state 0

Pulse On: Pulse output x to opposite of

current state then restore to

previous state ( pulsed output

is active 200 to 250 ms)

1

Hardware Output 1 State

2

Hardware Output 2 State

3

Hardware Output 3 State

4

Hardware Output 4 State

5

Hardware Output 5 State

6

Hardware Output 6 State

7

Hardware Output 7 State

8

All Hardware Outputs State

9

Hardware Output A Local Control

Latch On: Set Hardware Output x to relay

logic

10

Hardware Output 1 Local Control

11

Hardware Output 2 Local Control

12

Hardware Output 3 Local Control

13

Hardware Output 4 Local Control

14

Hardware Output 5 Local Control

15

Hardware Output 6 Local Control

16

Hardware Output 7 Local Control

17

All Hardware Outputs Local Control

18

43 Selector Switch Status

Latch On: Set x Selector Switch to 1

Latch Off: Set x Selector Switch to 0

Pulse On: Pulse x Selector Switch state

to opposite of the current state

then restore to previous state

(pulsed input is active 200 to

250 ms).

19

143 Selector Switch Status

20

243 Selector Switch Status

21

343 Selector Switch Status

22

Setting Group 0

Latch On: Select Group x to be Active

23

Setting Group 1

24

Setting Group 2

25

Setting Group 3

5-4