SECTION 5 • POINT LIST

Binary Input Points

Binary Input changes are scanned every four milliseconds. Events are pending in the Slave application

buffer until the Master device sends conformation that response with pending events was received. Table

5-1 describes the binary input points.

Table 5-1. Binary Input Points

Binary Input Points

Static Object Number: 1

Change Event Object Number: 2

Request Function Codes Supported: 1 (read)

Static Variation Reported When Variation 0 Requested: 1 (Binary Input Without Status)

Change Event Variation Reported When Variation 0 Requested: 2 (Binary Input Change With Time)

Point

Index

Description

Change Event

Assigned

Class (1,2,3 or

none)

Notes

0

50T Phase A Tripped

1

1

50T Phase B Tripped

1

2

50T Phase C Tripped

1

3

150T Phase A Tripped

1

4

150T Phase B Tripped

1

5

150T Phase C Tripped

1

6

50T Neutral Tripped

1

7

150T Neutral Tripped

1

8

50T Negative Sequence Tripped

1

9

150T Negative sequence Tripped

1

10

Breaker Failure Tripped

1

11

51 Phase A Tripped

1

12

51 Phase B Tripped

1

13

51 Phase C Tripped

1

14

51 Neutral Tripped

1

15

51Q Tripped

1

16

62

1

17

162

1

18

43

1

19

143

1

20

243

1

21

343

1

22

79 Close Signal

1

23

79 Running

1

24

79 Locked Out

1

25

79 Reclose Fail

1

9289900792 Rev C

BE1-851E DNP Protocol

5-1