Analog output status points and control blocks, Analog output status points and control blocks -14, Table 5-7. breaker failure status format -14 – Basler Electric BE1-851E DNP3 Protocol User Manual

Page 34: Table 5-8. system status -14

Advertising
background image

15. BF status is the bit mapped variable with format as described in Table 5-7. Delta of 1 deviation will

cause en event.

Table 5-7. Breaker Failure Status Format

Value / Bit Mask (hex)

Description

0001

Breaker Operation Control State {1=Breaker Operation Enabled;

0= Breaker Operation Disabled}

0002

Breaker State {1=Breaker Opened; 0= Breaker Closed}

16. Delta of 1 bit (any change) will cause an event.
17. Read values for Hardware Output Control is 1 = Enabled, and 0=Disabled.
18. Read values for x43 AUX Virtual Switch Logic Mode are 0 for Disabled, 1 = ON/OFF PULSE, 2 =

ON/OFF, and 3= OFF/MOMENTARY ON.

19. Read values for Setting Group Mode is 0= Disabled, 1=discrete select, and 2= binary select.

Setting groups can be controlled via DNP object 12 if value is 1 or 2.

20. Read values for 101 Breaker Control Switch Mode is 0=Disabled and 1=Enabled.
21. Latched Targets Status format is described in Table 5-5 under Note 6 to Table 5-4. Delta of 1

deviation will cause an event. Latched Targets Status can be reset via object 41 point 7.

22. BE1-851E Relay System Status is represented as 4 part, 16-bit mapped variables. The four part

System Status is described in Table 5-8. (For more information, see the BE1-851E Instruction

Manual, Section 6, Reporting and Alarm Functions). Delta of 1 deviation will cause an event.

Table 5-8. System Status

Value/Bit Mask (hex) Part 1 Description

Part 2 Description Part 3 Description

Part 4 Description

0001h

50 Phase Tripped

BF Picked Up

Virtual Output A

Input Contact 1

0002h

150 Phase Tripped

51 Phase Picked Up Virtual Output 1

Input Contact 2

0004h

50 Neutral Tripped

51 Neutral Picked UP Virtual Output 2

Input Contact 3

0008h

150 Neutral Tripped

51 Q Picked Up

Virtual Output 3

Input Contact 4

0010h

50Q Tripped

62 Tripped

Virtual Output 4

101 TRIP

0020h

150Q Tripped

162 Tripped

Virtual Output 5

101 CLOSE

0040h.

BF Tripped

43

Virtual Output 6

101 SLIP CONTACT

0080h

51 Phase Tripped

143

Virtual Output 7

HMI Reset Key

0100h

51 Neutral Tripped

243

Virtual Output 8

Logic Alarm

0200h

51 Q Tripped

343

Virtual Output 9

Major Alarm

0400h

50 Phase Picked Up 79 Close

Virtual Output 10 Minor Alarm

0800h

150 Phase Picked Up 79 Enabled

Virtual Output 11 Output 1 Trip Coil Monitor

1000h

50 Neutral Picked Up 79 Lockout

Virtual Output 12 Setting Group 0

2000h

150 Neutral Picked Up 79 Reclose Fail

Virtual Output 13 Setting Group 1

4000h

50Q Picked Up

79 Block Output

Virtual Output 14 Setting Group 2

8000h

150Q Picked Up

Always False (zero) Virtual Output 15 Setting Group 3

Analog Output Status Points and Control Blocks

Table 5-9 lists both the Analog Status Points (Object 40) and the Analog Output Control Blocks (Object

41). It is important to note that Analog Output Status Points are not included into Class 0.
The Return Status Value for object 41 for all control operations may be 6 (hardware problem) due to a

value out of range, or a relay internal state. One of the reasons for rejection may be if another

communication port or front panel HMI is actively programming. For more information, see the BE1-851E

Instructional Manual, Section 10, Human-Machine Interface.

5-14

BE1-851E DNP Protocol

9289900792 Rev C