Pickup, Control, Accuracy – Basler Electric BE1-87G User Manual

Page 15: Dropout, Timing, Operating power input, Pickup -5, Operating power input -5, Table 1-1. power supply types -5

Advertising
background image

Pickup
Graphs of the actual operating characteristics are shown in Section 5, Testing and Setting.
Control
A front panel sensitivity switch permits selection of minimum differential (operate) current. This sensitivity

is constant for restraint currents less than the nominal current (5 Aac for sensing input range 1 or 1 Aac

for sensing input range 2).
Minimum Differential (Operate) Current
Sensing Input Range 1:

0.1, 0.15, 0.2, 0.4, 0.5, 0.8, or 1.6 A

Sensing Input Range 2:

0.02, 0.03, 0.04, 0.08, 0.10, 0.16, or 0.32 A

The ideal operating characteristic is approximated by the following equations∗:
Sensing Input Range 1:

For I

R

≤ 5 A: I

OP

= I

S

For I

R

> 5 A: I

OP

= I

S

+ 0.5 (I

R

− 5)

Sensing Input Range 2:

For I

R

≤ 1 A: I

OP

= I

S

For I

R

> 1 A: I

OP

= I

S

+ 0.5 (I

R

− 1)

I

R

is the restraint current, defined as the lesser of the input currents

I

OP

is the operate current

I

S

is the front panel setting

Accuracy
Sensing Input Range 1

For I

R

≤ 4 A:

±

5% of the operate pickup characteristic or ±25 mA, whichever is

greater

For I

R

> 6 A (20 A max.):

±

8% of the operate pickup characteristic or ±150 mA, whichever is

greater

Sensing Input Range 2

For I

R

≤ 0.8 A:

±

5% of the operate pickup characteristic or ±25 mA, whichever is

greater

For I

R

> 1.2 A (4 A max.):

±

8% of the operate pickup characteristic or ±150 mA, whichever is

greater

Dropout
>90% of operate characteristic
Timing
<30 ms at 10 times pickup setting, 70 ms maximum

Operating Power Input
Relay operating power may be obtained from a wide variety of external voltage sources. When ordering,

any one of five internal power supply types may be selected to match the operating power voltage level

available at your site. Available power supply types are listed in Table 1-1.

Table 1-1. Power Supply Types

Type

Input Voltage

Burden at Nominal

Nominal

Range

K (midrange)

48 Vdc

24 to 150 Vdc

2.75 W

J (midrange)

125 Vdc

120 Vac

24 to 150 Vdc

90 to 132 Vac

2.96 W

7.87 VA

L (low range)

24 Vdc

12 to 32 Vdc

2.85 W

Y (mid range)

48 Vdc

125 Vdc

24 to 150 Vdc

24 to 150 Vdc

2.75 W

2.96 W

Z (high range)

250 Vdc

230 Vac

68 to 280 Vdc

90 to 270 Vac

3.13 W

9.20 VA

The type L power supply initially requires 14 Vdc to begin operating. Once operating, the

voltage may be reduced to 12 Vdc and operation will continue.

9170800990 Rev N

BE1-87G General Information