Introduction, Relay operating precautions, Operational test procedure – Basler Electric BE1-87G User Manual

Page 57: Section 5 • testing and setting -1, Introduction -1, Relay operating precautions -1, Operational test procedure -1

Advertising
background image

SECTION 5 • TESTING AND SETTING

INTRODUCTION

Proper relay operation can be confirmed by performing the test procedures in this section. This section

also contains recommendations for selecting an appropriate sensitivity switch (operating current) setting.

Relay Operating Precautions
Before operating the relay, note the following precautions:

A minimum of 200 mA in the output circuit is required to ensure operation of current operated targets

(relays with style number xxx-xxB-xxxxx)

If a wiring insulation test is required, remove the connection plugs and withdraw the cradle from its

case

When the connection plugs are removed, the relay is disconnected from the operating circuit and will

not provide system protection. Before removing a relay from service, be sure that external operating

(monitored) conditions are stable.

The relay case must be hard-wired to earth ground with no smaller than 12 AWG copper wire. A

separate ground lead is recommended for each device.

OPERATIONAL TEST PROCEDURE

The procedures that follow verify proper operation of the BE1-87G relay


Restraint current applied to any one relay input must not exceed either of the following conditions:

10 amperes continuous or 250 amperes for 1 second (relay style number x1x-xxx-xxxxx)

2 amperes continuous or 50 amperes for 1 second (relay style number x2x-xxx-xxxxx)

Whenever this current level is exceeded, provisions must be made to cut off the sensing current as the

relay trips.

CAUTION

To avoid false tripping on three-phase relays, the upper connection plug must be

in place prior to inserting or removing the lower connection plug.

CAUTION

During testing, do not apply a continuous operate current greater than 3 Aac.

Sustained operate current higher than 3 Aac will increase the temperature in the

stabilizing reactor and cause insulation breakdown.

NOTE

Because of the reactance of the stabilizing reactors, the burden may be too high

for large values of operate current with solid-state test sets.
The internal stabilizing reactor in relays with single-phase sensing (style number

Sxx-xxx-xxxxx) may be bypassed by placing a jumper across the terminals

illustrated in Figure 5-1. The jumper used should be capable of carrying 5 Aac of

current.
To bypass the external stabilizing reactor used on relays with three-phase

sensing (style number Gxx-xxx-xxxxx), the current source may be connected

directly to the relay case terminals

9170800990 Rev N

BE1-87G Testing and Setting

5-1

Advertising