Setting example 2, Setting example 2 -9, Figure 5-7. motor differential application -9 – Basler Electric BE1-87G User Manual

Page 65

Advertising
background image

Figure 5-7. Motor Differential Application

Using the SFR 4 column of Table 5-1, a 0.8 ampere setting is indicated. However, based on the note

accompanying this table, choose the next higher setting of 1.6, because CT #1 has a T classification and

CT #2 has a C classification. The T classification indicates that the CT has significant secondary leakage

inductance which somewhat degrades the transient performance. This is a concern during motor starting

because a slowly decaying offset component develops in at least one phase.

Setting Example 2
Select the pickup setting for the generator application in Figure 5-8. In this application, the settings need

to be based on the probability of significant dissimilar CT saturation during an external fault. Since the

generator is resistance grounded, the three-phase fault current will be much larger than the ground fault

level. Moreover, the resistor will rapidly dampen any offset-current component. Accordingly, determine the

sub-transient current (I”

d

).

rating

CT

I

d

×

=

=

×

×

÷

=

6

.

4

30

8

.

138

200

15

.

0

)

3

16

.

4

(

1000

"

Since a three-phase fault is involved, one-way lead burden is used to determine the total CT burden.

Each phase CT carries just the burden for the lead of that phase.

(R

t

)

1

= R

l

+ R

w

= 0.22 + 0.14 = 0.36 ; (Vce)

1

= 50 ; R

t

< 0.007(Vce)

1

= 0.35

(R

t

)

2

= 0.09 + 0.10 = 0.19 ; (Vce)

2

= 100 ; R

t

< 0.007(Vce)

2

= 0.7

Inequality (1) is met with CT #2 but not with CT #1. However, since the maximum external fault current is

only 4.6 time the CT rating (versus the assumption of 20 times rated for inequality (1)), the application is

suitable.

SFR = (1000 ÷ 50) × (0.36 ÷ 0.19) = 3.8

Using the SFR 4 column of Table 5-1, a 0.8 ampere setting is indicated. However, based on the note

accompanying Table 5-1, choose the next higher setting of 1.6 because CT #1 has a T classification and

CT #2 has a C classification. The T classification indicates that the CT has significant secondary leakage

inductance which somewhat degrades the transient performance. This is a concern during motor starting

because a slowly decaying offset component develops in at least one phase.

9170800990 Rev N

BE1-87G Testing and Setting

5-9

Advertising