Connections, Internal connections, Control connections – Basler Electric BE1-87G User Manual

Page 46: Sensing connections, Connections -16, Internal connections -16, Control connections -16, Sensing connections -16

Advertising
background image

CONNECTIONS

Verify the relay model and style number before connecting and energizing the relay. Incorrect wiring may

result in damage to the relay. Except where otherwise noted, connections should be made with minimum

wire size of 14 AWG.

Internal Connections
Internal connections/terminal assignments for a single-phase relay are illustrated in Figure 4-15. Internal

connections/terminal assignments for a three-phase relay are illustrated in Figure 4-16. These figures

may show options that may not apply to your relay.

Control Connections
Typical dc control connections are shown in Figure 4-17.

Sensing Connections
Typical sensing current connections for a single-phase application are shown in Figure 4-18.
Three-phase sensing current connections are illustrated in Figure 4-19 and Figure 4-20. Figure 4-19

shows the sensing inputs connected in a wye configuration. Figure 4-20 shows the sensing inputs

connected in a delta configuration.

4-16

BE1-87G Installation

9170800990 Rev N