Maintenance, Storage, Maintenance -23 – Basler Electric BE1-87G User Manual
Page 53: Storage -23
Advertising
MAINTENANCE
BE1-87G relays require no preventive maintenance other than the periodic inspection of the relay case
and stabilizing reactor terminal connections to ensure that they are clean and tight. If repairs are needed,
contact the Technical Sales Support department at Basler Electric for assistance.
STORAGE
This device contains long-life electrolytic capacitors. For devices that are not in service (spares in
storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once per
year.
9170800990 Rev N
BE1-87G Installation
4-23
Advertising