4 vent terminal clearances – Continental Fireplaces CLHD45 User Manual

Page 12

Advertising
background image

12

W415-0895 / C / 03.13.12

3.4 VENT TERMINAL CLEARANCES

INSTALLATIONS

CANADA

U.S.A.

A

12”

12”

Clearance above grade, veranda porch, deck or balcony.

B

12”

Δ

9”

Δ

Clearance to windows or doors that open.

C

12” *

12” *

Clearance to permanently closed windows.

D

18” **

18” **

Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’ from
the center line of the terminal.

E

12” **

12” **

Clearance to unventilated soffi t.

F

0”

0”

Clearance to an outside corner wall.

G

0” ***

0” ***

Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).

2” ***

2” ***

Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).

H

3’

3’ ****

Clearance to each side of the center line extended above the meter / regulator assembly to a maximum
vertical distance of 15’.

I

3’

3’ ****

Clearance to a service regulator vent outlet.

J

12”

9”

Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.

K

6’

3’ †

Clearance to a mechanical air supply inlet.

L

7’ ‡

7’ ****

Clearance above a paved sidewalk or paved driveway located on public property.

M

12” ††

12” ****

Clearance under a veranda, porch or deck.

N

16”

16”

Clearance above the roof.

O

2’ †*

2’ †*

Clearance from an adjacent wall including neighbouring buildings.

P

8’

8’

Roof must be non-combustible without openings.

Q

3’

3’

See chart for wider wall dimensions.

R

6’

6’

See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an open-
ing between the terminal and the open side of the structure.

S

12”

12”

Clearance under a covered balcony

Δ

The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.

*

Recommended to prevent condensation on windows and thermal breakage

**

It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.

***

The periscope requires a minimum 18 inches clearance from an inside corner.

****

This is a recommended distance. For additional requirements check local codes.

3 feet above if within 10 feet horizontally.

A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.

††

Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.

†*

Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.

††*

Permitted only if the balcony is fully open on a minimum of one side.

12.1C

NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.

COVERED BALCONY APPLICATIONS

††*

Q

MIN

R

MAX

MAX

R

= 3 feet

= 2 x

”  feet

Q

ACTUAL

R

Q

S

G

P

Advertising