Warning, 0 installation – Continental Fireplaces CLHD45 User Manual

Page 19

Advertising
background image

19

W415-0895 / C / 03.13.12

For optimum performance it is recommended that all horizontal runs have a minimum of 1/4” rise per foot. For
safe and proper operation of the appliance, follow the venting instructions exactly.

!

WARNING

FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS

EXACTLY.

ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED

RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC

W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR

WHICH MUST BE SEALED USING MILL PAC.

IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO

ENSURE THE CONNECTION CANNOT SLIP OFF.

DO NOT CLAMP THE FLEXIBLE VENT PIPE.

RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING

SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT

VENT SECTIONS PER INSTALLATION INSTRUCTIONS.

RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.

REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO

MAINTAIN CLEARANCES TO COMBUSTIBLES.

68.2A

!

WARNING

DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF

MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.

ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.

INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR

OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.

70.1

For shipping purposes, the heat shield has been attached on top of the appliance.

If venting with a 90 degree elbow directly off of the top of the appliance, the elbow heat shield must be reposi-

tioned and secured with the two screws (supplied) as illustrated.

The heat shield can be adjusted up to a maximum of 18”. Remove the two screws as illustrated to adjust the
shield. If the elbow height exceeds this height, the use of the shield is no longer required.

REMOVE SCREWS

TO ADJUST

HEIGHT

18”

MAX

3.11 VENT HEAT SHIELD INSTALLATION

4.0 INSTALLATION

4.1 WALL AND CEILING PROTECTION