3.10 VERTICAL THROUGH EXISTING CHIMNEY

7.6

This appliance is designed to be attached to a 3” co-linear aluminum fl ex vent system running the full length
of a masonry chimney.

The fl ex liners accommodate any contours of a masonry chimney, however, it is necessary to keep the fl exible
liners as straight as possible. The inlet air collar of the termination cap must be connected to the air intake fl ex
liner and the exhaust collar must be connected to
the exhaust fl exible liner.

Both Simpson Duravent and Selkirk co-linear
to co-axial adaptors have been approved on
this appliance (NOTE: A vent adaptor will be
required directly off the appliance

).

Follow vent manufacturer’s installation
instructions.

Different manufacturer’s venting components
must not be combined. Once the preferred
manufacturer’s appliance adaptor has been
attached, the remainder of the system must
be that of the same manufacturer.

The only exception to this rule is to use Wolf
Steel’s approved 3” fl ex liner and co-linear
termination.

!

WARNING

RISK OF FIRE!

CO-AXIAL TO CO-LINEAR VENTING CONFIGURATIONS MUST ONLY BE USED IN A NON-

COMBUSTIBLE CHIMNEY OR ENCLOSURE. INSTALLATION IN A COMBUSTIBLE ENCLOSURE COULD

RESULT IN A FIRE.

AIR

INTAKE

EXHAUST

FLUE

FLEX

LINER

*

40 FT

MAX.

10 FT

MIN

COAXIAL TO

CO-LINEAR

ADAPATER

APPLIANCE

VENT ADAPTOR

TERMINATION

* Measured from appliance fl ue collar
to termination fl ue collar