Continental Fireplaces CLHD45 User Manual

Page 27

Advertising
background image

27

W415-0895 / C / 03.13.12

* When constructing the enclosure allow for fi nishing material thickness to maintain clearances.
** HORIZONTAL VENT SECTIONS:

A minimum clearance of 2” to the top and 1” to the sides and bottom of

the vent pipe on all horizontal runs to combustibles is required. Horizontal vent sections within enclosures re-
quire a minimum clearance of 6” at the top of the vent pipe, see “MINIMUM CLEARANCE TO COMBUSTIBLE
ENCLOSURES” section. Use fi restop spacer W010-1777 (supplied).
** VERTICAL VENT SECTIONS:

A minimum of 1” all around the vent pipe on all vertical runs to combustibles

is required except for clearances in appliance enclosures. Vertical vent sections within enclosures require a
minimum clearance of 2” around the vent pipe. Use fi restop spacer W500-0096 (not supplied).

FRAMING

MAINTAIN THESE MINIMUM CLEARANCES TO COMBUSTIBLES FROM

APPLIANCE AND VENT SURFACES:

ROUGH OPENING

HEIGHT

WIDTH

DEPTH

TO CEILING

FROM BASE

OF

APPLIANCE

TO CEILING

FROM TOP

OF

APPLIANCE

OPENING

SIDE

WALL

TO COMBUSTIBLE

FINISHING ABOVE

APPLIANCE

TOP

OF

VENT

PIPE

SIDES AND

BOTTOM
OF VENT

PIPE

REAR & SIDE

STANDOFFS

41 ¼”

46 ¾”

20 ¹/

8

”*

56”

30 ¹¹/

16

2”

14”

2”**

1”**

0”

ǩ´

´

ǩ´

ô´

ô´

ò´

ô´

BACK WALL OF CHASE /
ENCLOSURE (INCLUDING ANY
FINISHING MATERIAL)

INSIDE

CHASE

OUTSIDE

CHASE