Continental Fireplaces CLHD45 User Manual

Page 15

Advertising
background image

15

W415-0895 / C / 03.13.12

(H

T

) > (V

T

)

Simple venting configuration (only one 90° elbow)

See graph to determine the required vertical rise V

T

for the

required horizontal run H

T

.

REQUIRED

VERTICAL

RISE IN

INCHES V

T

HORIZONTAL VENT RUN PLUS OFFSET IN FEET H

T

For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: H

T

< 4.2 V

T

Formula 2: H

T

+ V

T

< 24.75 feet

Example:
V

1

= V

T

= 6 FT

H

1

= 3 FT

H

2

= 5 FT

H

R

= H

1

+ H

2

= 3 + 5 = 8 FT

H

O

= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7 FT

H

T

= H

R

+ H

O

= 8 + 2.7 = 10.7 FT

H

T

+ V

T

= 10.7 + 6 = 16.7 FT

Formula 1:

H

T

< 4.2 V

T

4.2 V

T

= 4.2 x 6 = 25.2 FT

10.7 < 25.2

Formula 2:

H

T

+ V

T

< 24.75 FT

16.7 < 24.75

Since both formulas are met, this vent configuration is acceptable.

0

5

15

20

100

50

150

12.5’

8”

57”

147”

2’

The shaded area within the lines represents acceptable

values for H

T

and V

T

90°

V

1

H

1

H

2

90°

Example:
V

1

= 4 FT

V

2

= 1.5 FT

V

T

= V

1

+ V

2

= 4 + 1.5 = 5.5 FT

H

1

= 2 FT

H

2

= 1 FT

H

3

= 1 FT

H

4

= 1.5 FT

H

R

= H

1

+ H

2

+ H

3

+ H

4

= 2 + 1 + 1 + 1.5 = 5.5 FT

H

O

= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT

H

T

= H

R

+ H

O

= 5.5 + 8.1 = 13.6 FT

H

T

+ V

T

= 13.6 + 5.5 = 19.1 FT

Formula 1:

H

T

< 4.2 V

T

4.2 V

T

= 4.2 x 5.5 = 23.1 FT

13.6 < 23.1

Formula 2:

H

T

+ V

T

< 24.75 FT

19.1 < 24.75

Since both formulas are met, this vent configuration is acceptable.

90°

90°

90°

90°

H

1

H

2

V

1

V

2

H

3

H

4

10

19.5’

16.8

NOTE: There MUST be a 25% reduction in total horizontal length (H

T

) when using fl ex vent.

Advertising