Section 3-2-1: venting layout, Pvtk-1), Installation – Montigo P42DF User Manual

Page 10

Advertising
background image

Figure 9. Top vent, Roof mounted termination with no offset in vent run.

Figure 9a. Top vent, Roof mounted with 1 offset (1 offset= two 90°

bends).

Figure 9b. Top vent, Roof mounted with 2 offsets (1 offset= two 90°

bends).

Roof mounted Terminations
The following details are some possible configurations for Roof mounted

terminations.

Support ring

Support plate

Firestop

32’ max.

2’ min.

PVTK1

Termination

Support ring

Support plate

Firestop

32’ max.

2’ min.

Obstacle

PVTK1

Termination

Section 3-2: Installing a Roof Mounted Direct

Vent Termination (PVTK-1)

This section applies to installations where the direct vent termi-

nation will be roof mounted.

Section 3-2-1: Venting Layout

Selection of components and details of venting lay out should

adhere to the following guidelines:

„

The maximum termination point is 32’ above the fireplace (NOTE:

if the maximum termination height is used, the flame pattern

may be affected).

„

The Vertical termination must be a minimum 2’ higher than where

the termination exits the roofing materials, (asphalt shingles,

cedar shakes, etc). This distance should be measured from the

high side of the roof slope where the flue flashing intersects the

roofing materials. (see Figures 9 to 9c).

„

Termination location must be a minimum 6’ from a mechanical

air inlet.

„

For a more detailed diagram of allowed termination locations,

see Appendix A.

„

A maximum of two offsets (each offset is made up of 2-90°

bends) may be made for vertical vent runs.

„

Firestops must be installed as required by National & local codes

„

Ensure all horizontal runs are supported with a minimum of 3

supports per 10’ of venting.

„

Install all roof flashing and storm collars as shown.

Support straps or

support plate & ring

2’ min.

Firestop

Firestop

Firestop

32’ max

Support plate

& ring

Obstacle

PVTK1

Termination

PEXT

PXT-10

Adaptor

Flue

Collar

Page 10

P42DF* Indoor Gas Fireplace

XG0195 - 150204.2

Installation