Installation, Warning – Montigo P42DF User Manual

Page 14

Advertising
background image

Figure 14. Rear Vent Venting Graph for NG and LP wall mounted

terminations.

Figure 14b. Rear Vented, wall mounted Multi-elbow termination

installation. The vent run must comply with the Venting Graph for Rear

vent, wall mounted terminations, Figure 14.

Figure 14a. Straight run, Rear Vented, wall mounted termination. The

vent run must comply with the Venting Graph for Rear vent, wall mounted

terminations, Figure 14.

Notes Wall Mounted Terminations: Rear Vent

■ All dimension lengths for vertical or horizontal runs are measured

from center of the vent pipe.

■ Venting runs must fall within the limits set by the venting graphs,

see Figure 14.

■ Fireplace must be converted to Rear Vent configuration prior to

running vent, see Figure 8 and 8a.

The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of the

termination and the horizontal run from the fireplace flue collar to the wall

flange of the termination. Plot on the Venting Graph Figure 14 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal

run to the wall flange of the vent termination is 138", this would be an

acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 48" and the horizontal run

to the wall flange of the vent termination is 72", this would not be an

acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 60" and the

horizontal run to the wall flange of the vent termination is 144", this

would not be an acceptable installation.

27 1/2”

PXT Extension

RHS101 Heat

Shield

Termination

Hearth

Exterior

Wall

NOTE:

12” MAX. horizontal

run with no vertical lift.

12” MAX.

30” Max.

53” Min

12”

Max.

Flex or Rigid

Section

25 1/5”

Min.

27 1/2”

42”

53”

A

C

B

Acceptable vent run

within non-shaded area.

If your installation does not fall within

the venting parameters, please

contact a local Montigo dealer for

Power Venting options.

Unacceptable vent run

within shaded area.

12”

27.5”

WARNING:

An inspection of the explosion relief flappers and door MUST be

made prior to lighting the fireplace. A faulty seal on the door gasket ...

and/or explosion ports will result in products of combustion leaking

into the living space and may result in carbon monoxide poisoning.

Note: Images are shown without screens for clarity purposes. However,

your fireplace should not be operated without proper installation of

screens.

Page 14

P42DF* Indoor Gas Fireplace

XG0195 - 150204.2

Installation