Installation – Montigo P42DF User Manual

Page 15

Advertising
background image

Figure 15. Corner (Rigid) installation. (NG Models Only)

Figure 15a. Corner (Flex) installation. (NG Models Only)

45° Corner Installation.

Attach an PEL-45 (45° elbow) directly onto the flue collar. Cut the PXT-

20 to suit, and attach it to the PEL-45. Slide the fireplace into position

and attach to the termination.

45° or less Corner Installation.
Use an PTO-4 termination and an PFL-1 or PFL-2 (12" or 24"

compressed length) and a frame, if appropriate. Flex may be turned

to obtain desired degree of angle required but must not exceed 45°.

Note: Through the wall venting kits are also available for both

the Straight and the Corner Installation. The Kit includes a heat

shield, a PFL-18 (f/f) flexible pipe, and a termination with or without

a mounting frame.

PEL-45 Elbow

PEL-90 Elbow

PXT-18

IMPORTANT:

Corner Installation is available for P42DF

Top Vent Units Only. Ensure minimum

Vertical Venting Height of 48" is maintained

in corner installations.

Note: Images are shown without screens for clarity purposes. However,

your fireplace should not be operated without proper installation of

screens.

Page 15

P42DF* Indoor Gas Fireplace

XG0195 -150204.2