The Venting Graph: P42DF*
Measure the vertical height from the fireplace hearth to the centre of

the termination and the horizontal run from the fireplace flue collar to

the wall flange of the termination. Plot on the Venting Graph Figure 12

or 13 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the

installation is acceptable.
Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 120" and the horizontal

run to the wall flange of the vent termination is 144", this would be

an acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 36" and the horizontal

run to the wall flange of the vent termination is 84", this would not

be an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 60" and

the horizontal run to the wall flange of the vent termination is 144",

this would not be an acceptable installation.

Figure 13. Top Vented, wall mounted installation with one 90° bend.

The vent run must comply with Venting Graph for Top vent, wall
mounted terminations, Figure 12 or 12a

.

Figure 13a. Top Vented, wall mounted Multi-elbow installation.

The vent run must comply with Venting Graph for Top vent, wall
mounted terminations, Figure 12 or 12a

.

Section 3-3-1: Venting Layout: Wall mounted termination.
Selection of components and details of venting layout should adhere

to the following guidelines:

„

Vent terminations must not be recessed in walls or siding.

„

For Heat Shield requirements see Section 3-3-3 on page 16.

„

Once the proposed venting layout has been determined refer

to Figure 12, 12a, or 14 to ensure the layout is acceptable.

Notes Wall Mounted Terminations: TOP VENT

„

All measurements for vertical or horizontal runs are measured

from center of the vent pipe.

„

Venting runs must fall within the limits set by the venting graph,

see Figure 12 or 13

Wall mounted Terminations
The following details are some possible configurations for Wall mounted

terminations.

Solid Section

Flex Section

Hearth

30”min

15’foot Max.

Shield

Termination

Exterior

Wall

8' MIN AT MAX

Horizontal

Figure 12. P42DF* LP Top Vent Venting Graph for wall mounted

terminations.

Figure 12a. P42DF* NG Top Vent Venting Graph for wall mounted

terminations.

12”

53”

A

C

B

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

If your installation does not fall

within the venting parameters,

please contact a local Montigo

dealer for Power Venting options.

44”

40 1/2”

A

C

B

.

Unacceptable vent run

within shaded area.

Acceptable vent run

within non-shaded area.

If your installation does not fall

within the venting parameters,

please contact a local Montigo

dealer for Power Venting options.

Heat

Heat

Shield

Termination

Hearth

Exterior

Wall

40 1/2" Min. (NG)

Flex section

53 Min. (LP)

44" Max. (NG)

12 Max. (LP)

Page 13

P42DF* Indoor Gas Fireplace

XG0195 -150204.2