Online power – OnLine Power Telecommunication User Manual

Page 16

Advertising
background image

OnLine Power

1-1

REV A

SECTION 1 - INTRODUCTION

1-1 OVERVIEW

Within each Power Backup Cabinet is an Uninterruptible Power Supply (UPS). The purpose of this device is to
provide power to the critical load during brown out, or black out conditions, without disruption of operation of the load
equipment. When the unit operates in the backup mode, the AC power for the load comes from a set of internal
batteries and Inverter. The battery charger keeps the batteries charged and ready to fulfill the unit’s function to
supply reserve power.

Also, PBC-II cabinet provides an additional level of power protection from transients, surges, electrical noise, and
other power disturbances.

What differentiates this PBC-II from, off-the-shelf, UPS equipment is the high level to which these units have
been ”hardened” ( ruggedized ) to ensure continuous operation in very harsh environments, particularly outdoors.

1-2 FEATURES
Status Indicators

The unit has two major components, the Electronic Tray and Battery. The Electronic Tray contains the battery
charger, breakers, receptacles, LED status panel, Inverter circuitry, and the input/output terminals. Each of the two
lower tray holds four batteries on each shelf. The lights on the LED status panel (at the front panel display) indicates
the unit’s operational mode. (See Illustration 1-1 below) These lamps provide a positive visual indication of specific
aspects of the unit’s functional operation. These are as follows:

OVERLOAD (Red LED)

The output load is over 100% of rated load.

100% (Green LED)

Full load of 100% rating.

(Green LED)

75% of rated load.

(Green LED)

50% of rated load.

25% (Green LED)

0 to 25% of rated load.

SUMMARY ALARM (Red LED)

Illuminates when unit shutdown alarm condition is present

such as over temp., output short circuit, output overload, &

DC

overvoltage

HIGH BATTERY CAPACITY (Green LED)

Indicates the batteries are fully charged

MEDIUM BATTERY CAPACITY (Green LED)

Indicates the batteries are half charged

LOW BATTERY (Red LED)

Indicates the battery is approaching low shutdown level.

ON BATTERY (Green LED)

Indicates the battery is ON, and output is supplied from battery.

BYPASS ON (Green LED)

Indicates the unit is running with AC input power in OFF Line,

AC Mode, in Bypass.

INVERTER ON (Green LED)

Indicates the unit is running with the battery power in Inverter

mode.
INPUT AC ON (Green LED)

Indicates the input power is present.

UPS OFF S1

Used only to shut-off UPS when unit is running in DC mode.

UPS ON S2

Used only to turn on UPS when unit is running in DC mode.

Advertising