Online power – OnLine Power Telecommunication User Manual

Page 37

Advertising
background image

OnLine Power

3-7

REV A

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

G

(-)

(+)

DOOR

SWITCH

INPUT

POWER

INPUT

HEATER

VOLTAGE

CB7

CB6

OUTPUT POWER

CB5

CB4

G

N

L

G

N

L

G

N

L

G

N

L

G

N

L

G

N

L

TO ADJUNCT BATTERY CABINET

CONNECTIONS AT TB1 OF MAIN UPS CABINET

ILLUSTRATION 3-3

TB1-1

INPUT VOLTAGE - HOT LINE

TB1-2

INPUT VOLTAGE - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES

TB1-3 INPUT

GND

TB1-4

OUTPUT #1 - HOT LINE

TB1-5

OUTPUT #1 - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES

TB1-6

OUTPUT #1 - GND

TB1-7

OUTPUT #2- HOT LINE

TB1-8

OUTPUT #2 - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES

TB1-9

OUTPUT #2 - GND

TB1-10

OUTPUT #3- HOT LINE

TB1-11

OUTPUT #3 - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES

TB1-12

OUTPUT #3 - GND

TB1-13

OUTPUT #4- HOT LINE

TB1-14

OUTPUT #4 - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES

TB1-15

OUTPUT #4 - GND

TB1-16

HEATER VOLTAGE - HOT LINE FOR OPTIONAL ADJUNCT BATTERY CABINET

TB1-17

HEATER VOLTAGE - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES. ROUTE
WITH TB1-16

TB1-18

GND. ROUTE WITH TB1-16

TB1-19

DOOR SWITCH (N/O) FROM OPTIONAL ADJUNCT BATTERY CABINET

TB1-20

DOOR SWITCH (N/O) RTN FROM OPTIONAL ADJUNCT BATTERY CABINET

TB1-21

+96VDC FROM OPTIONAL ADJUNCT BATTERY CABINET

TB1-22

-96VDC FROM OPTIONAL ADJUNCT BATTERY CABINET

TB1-23

GND FROM OPTIONAL ADJUNCT BATTERY CABINET