• Load Testing

• Load Testing shall only be performed as a bench test.

• While on open circuit, place 100 amp load across each battery for a period of 30 seconds.

• Measure and record end of discharge (E.O.D.) voltage at 30 seconds.

• Calculate average and compare results against value of 10.95 for Type PRC 12120X E.O.D.@ 30

Seconds and 100 amp load.

• If calculated average E.O.D. of group is observed as being normal, identify and replace individual

batteries with values that are 10% less than the group average.

• General Equipment Requirements.

• Digital voltmeter- 3 1/2 digit, minimum 0.25% accuracy.

• Load tester (100 amps) with digital voltage readout, minimum 0.25% accuracy.

• Thermometer-

thermocouple,

contact type, 1 0 C accuracy.

• Battery Date Coding.

• The manufacturer stamps the Negative terminal post of the battery, with the month and year date

code.

• Shelf life is based on normal storage temperature conditions, 66

o

F ~ 90

o

F, and requires recharging

every 6 months from the last full charge date.

WARNING!

BATTERY SHELF TIME, WHEN STORED UNDER TEMPERATURE
CONDITIONS OF 66

O

F ~ 90

O

F, IS FIVE ( 5 ) MONTHS MAXIMUM AFTER THE

SHIP DATE.
BATTERY MUST BE RECHARGED AFTER THIS DATE OTHERWISE THEY
WILL BE DAMAGED.
THE SHIP DATE IS PART OF THE SERIAL NUMBER,
EXAMPLE S/N 00 L7 02 00####
YEAR MONTH UNIT I.D. NUMBER