350-2100 cfm Dryers

Chapter 4: Control Panel

22 of 58

VALVE POSITION ERROR

A pair of position switches confirm proper shifting of the valves.

If full travel is not confirmed by the switches, the cycle will not begin on the new bed.

4-2 Switches and Meters

ON/OFF SELECTOR SWITCH

This energizes or de-energizes the dryer's control power.

START/STOP PUSH-BUTTON

Press this momentary contact switch to start the dryer. Press this switch to shut down an
operating dryer. The dryer shutdown sequence is:

1. Process heaters shut off immediately.

2. Process blower continues to run for 20 minutes to cool the process heater, then shuts

off.

3. The regeneration cycle of the off-line bed will continue until finished, the

regeneration heaters will shut off, followed by the regeneration blower.

DEWPOINT METER

;

This meter indicates the current process air delivery moisture content.

;

When the Push To Set button is pressed, the meter indicates the Dewpoint Shift

point. See Section 5-10.

PUSH TO SET

This push-button is used when setting or confirming the Dewpoint Shift point. See Section 5-
6.

DEWPOINT SHIFT ADJUST

This potentiometer [pot] is used when setting the Dewpoint Shift point. See Section 5-6.

SHIFT SET SELECTOR SWITCH

In the "ON" position, the drying temperature is raised or lowered to the ¼ DIN controller's
alternate temperature - see Section 4-5.

OVER TEMPERATURE RESET [Optional]

This push-button resets the control system to allow restart of heaters and blowers after
process air temperature has dropped below the high value programmed into the 1/8 DIN
panel meter (4CNTL)

This is on dryers equipped with the auxiliary hi-temperature safety option.

HEATER BURN-OUT INDICATOR METERS [Optional]

;

The six current indicating meters monitor the current draw on each phase of the

process and regeneration heaters.

;

During normal operation, all three meters (phases) should read within one or two

amps of each other.