Chapter 6: Maintenance

48 of 58

6-12 Regeneration Monitor Advanced Programming

The regeneration monitor has three menu levels, numbered 0 through 2. Each menu level allows
specific parameters to be viewed and/or set.

Moving Between Levels
Level 0, the RUN mode, is the default and automatically appears when the dryer is powered up. To

move to Level 1, press and hold

for 2 seconds. When Level 1 is reached, press and hold both

and

for 1 second to move up a level, or move back to RUN mode by pressing

for 1 second.

See the flow chart below.

Comparative output settings (when security is enabled)
Output hysteresis
Input shift value
Linear output range
Security protection

Sensor type
Display unit (°F/°C)
Display refresh time
Communication unit

Process temperature
Comparative output settings (when security is disabled)

Level 0

Level 1

Level 2

Press

2 sec.

Press 1

sec.

Press

1 sec.

+

Press 1

sec.

Press

1 sec.

+



LEVEL 0
In this, the default level, the present regeneration
bleed air temperature is displayed, plus the
monitor’s four setpoints can be viewed and
changed.

If security is enabled, the setpoints cannot be

changed. They may be reviewed by pressing

.

If security is disabled, the setpoints can be

changed on this level by using

and

.

When the desired setpoint is displayed, press

to move to the digit you want to change, and use

to change the digit. Then press

to save

the new setting to memory and to move on to the
next setpoint.

LL Set Value

Low Regen Temp Alarm

L Set Value

Regen Blower Shutdown Temp

H Set Value

Closed Loop Regen Cool Down Temp

HH Set Value

Heater Cut Off Temp

Present Value (PV)

Regen Bleed Air Temp