E2: motor 1 parameters, E2-01: motor rated current, E2-02: motor rated slip – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 194

Advertising
background image

No.

Parameter Name

Setting Range

Default

E1-11

Middle Output Frequency 2

0.0 to [E1-04]

0.0 Hz

<6>

E1-12

Middle Output Frequency Voltage 2

0.0 to 255.0 V

<4>

0.0 V

<5>

<6>

E1-13

Base Voltage

0.0 to 255.0 V

<4>

0.0 V

<5>

<7>

<4> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<5> The drive changes these settings when Auto-Tuning is performed (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
<6> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<7> E1-13 and E1-05 are set to the same value when Auto-Tuning is performed.

Output Voltage (V)

Frequency (Hz)

E1-05
E1-12

E1-13

E1-08

E1-10

E1-09

E1-07 E1-06 E1-11 E1-04

Figure 5.35 V/f Pattern

Note:

1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 equal to E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the drive is initialized, but E1-04 through E1-13 return to their default values.
4. Only use E1-11, E1-12, and E1-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.

u

E2: Motor 1 Parameters

These parameters contain the motor data needed for motor 1. Performing Auto-Tuning (including Rotational Auto-Tuning

and Stationary Auto-Tuning 1 and 2) automatically sets these parameters.

Refer to Auto-Tuning Fault Detection on page

321

for details if Auto-Tuning cannot be performed.

n

E2-01: Motor Rated Current

Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on

the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.

No.

Parameter Name

Setting Range

Default

E2-01

Motor Rated Current

10% to 200% of the drive

rated current

<1>

Determined by

o2-04

<1> Display is in the following units:

2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.

Note:

An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly to

prevent this error.

n

E2-02: Motor Rated Slip

Sets the motor rated slip in Hz to provide motor control, protect the motor, and calculate torque limits. This value is

automatically set during Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 1 and 2).

No.

Parameter Name

Setting Range

Default

E2-02

Motor Rated Slip

0.00 to 20.00 Hz

Determined by

o2-04

If Auto-Tuning cannot be performed, calculate the motor rated slip using the information written on the motor nameplate and

the formula below:
E2-02 = f - (n × p)/120
(f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles)

5.5 E: Motor Parameters

194

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual