O3: copy function, O4: maintenance monitor settings – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 271

Advertising
background image

Setting 0: Disabled
Setting 1: Enabled

u

o3: Copy Function

These parameters control the Copy function of the digital operator. The Copy function stores parameter settings into the

memory of the digital operator to facilitate the transfer of those settings to other drives that are the same model, capacity, and

same control mode setting.

Refer to Copy Function Related Displays on page 324

for a description of errors and displays.

n

o3-01: Copy Function Selection

Instructs the drive to Read, Write, or Verify parameter settings.

No.

Name

Setting Range

Default

o3-01

Copy Function Selection

0 to 3

0

Setting 0: Copy Select (No Function)

Setting 1: INV --> OP READ

Copies all parameters from the drive to the digital operator.

Note:

Set o3-02 to 1 to unlock copy protection.

Setting 2: OP --> INV WRITE

Copies all parameters from the digital operator to the drive.

Setting 3: OP<-->INV VERIFY

Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.

n

o3-02: Copy Allowed Selection

Allows and restricts the use of the Copy function.

No.

Name

Setting Range

Default

o3-02

Copy Allowed Selection

0, 1

0

Setting 0: Disabled
Setting 1: Enabled

u

o4: Maintenance Monitor Settings

n

o4-01: Cumulative Operation Time Setting

Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of

operation time from some desired value. Total operation time can be viewed in monitor U4-01.

Note:

The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also

be displayed in monitor U4-01.

No.

Name

Setting Range

Default

o4-01

Cumulative Operation Time Setting

0 to 9999

0

n

o4-02: Cumulative Operation Time Selection

Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in monitor U4-01.

No.

Name

Setting Range

Default

o4-02

Cumulative Operation Time Selection

0, 1

0

Setting 0: Power On Time

The drive logs the time it is connected to a power supply, regardless of whether the motor is running.

Setting 1: Run Time

The drive logs the time that the output is active including when the Run command is active (even if the motor is not rotating)

and when there is voltage output.

5.10 o: Operator Related Settings

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

271

5

Parameter Details