E2-03: Motor No-Load Current

Set the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive sets

E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor no-load current

listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to receive a copy of the

motor test report.

No.

Parameter Name

Setting Range

Default

E2-03

Motor No-Load Current

0 to [E2-01]

(unit: 0.01 A)

Determined by

o2-04

Note:

The number of decimal places in the parameter value depends on the drive model 1. This value has two decimal places (0.01 A) if the drive

is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motor

capacity is higher than 11 kW.

Refer to Power Ratings on page 396

for details.

n

E2-04: Number of Motor Poles

Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically

be saved to E2-04.

No.

Parameter Name

Setting Range

Default

E2-04

Number of Motor Poles

2 to 48

4

n

E2-05: Motor Line-to-Line Resistance

Sets the line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully, this value is automatically

calculated. Enter this value as line-to-line and not for each motor phase.
If Auto-Tuning is not possible, contact the motor manufacturer to find out the line-to-line resistance or measure it manually.

When using the manufacturer motor test report, calculate E2-05 by one of the formulas below:
• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C.

No.

Parameter Name

Setting Range

Default

E2-05

Motor Line-to-Line Resistance

0.000 to 65.000 mΩ

<1>

Determined by

o2-04

<1>

n

E2-06: Motor Leakage Inductance

Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. This value is automatically set

during Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).

No.

Parameter Name

Setting Range

Default

E2-06

Motor Leakage Inductance

0.0 to 40.0%

Determined by

o2-04

n

E2-10: Motor Iron Loss for Torque Compensation

Sets the motor iron loss in watts.

No.

Parameter Name

Setting Range

Default

E2-10

Motor Iron Loss for Torque Compensation

0 to 65535 W

Determined by

o2-04

n

E2-11: Motor Rated Power

Sets the motor rated power in kW. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be

saved to E2-11.

No.

Parameter Name

Setting Range

Default

E2-11

Motor Rated Power

0.00 to 650.00 kW

Determined by

o2-04

5.5 E: Motor Parameters