Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 203

Advertising
background image

No.

Parameter Name

Setting Range

Default

F6-56

DeviceNet Speed Scaling

-15 to 15

0

F6-57

DeviceNet Current Scaling

-15 to 15

0

F6-58

DeviceNet Torque Scaling

-15 to 15

0

F6-59

DeviceNet Power Scaling

-15 to 15

0

F6-60

DeviceNet Voltage Scaling

-15 to 15

0

F6-61

DeviceNet Time Scaling

-15 to 15

0

Setting

The monitor value in the AC/DC Drive Object 2AH is calculated by:

AC/DC Drive Object 2AH Monitor = Drive Value × 2

Scaling

Example:
If the drive output frequency monitor (U1-02) is 5.00 and the scaling is set to F6-56 = 6, then the value in the AC/DC Drive

Object 2AH, Instance 1, Attribute 7 would be 500 × 2

6

= 32000.

n

F6-62: DeviceNet Heartbeat Interval

Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the heartbeat function.

No.

Parameter Name

Setting Range

Default

F6-62

DeviceNet Heartbeat Interval

0 to 10

0

n

F6-63: DeviceNet Network MAC ID

Displays the MAC ID assigned to the drive. F6-63 is used only as a monitor.

No.

Parameter Name

Setting Range

Default

F6-63

DeviceNet Network MAC ID

0 to 63 (read only)

63

n

F6-64 to F6-71: Dynamic Assembly Parameters (Reserved)

5.6 F: Option Settings

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

203