Temperature derating – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 411

Advertising
background image

Three-Phase 600 V Class

Drive Model

Rated Current [A]

Normal Duty Rating (ND)

2 kHz

5 kHz

8 kHz

10 kHz

5A0062

62.0

61.3

49.7

41.9

5A0077

77.0

76.2

61.7

52.0

5A0099

99.0

80.0

55.1

Three-Phase 600 V Class

Drive Model

Rated Current [A]

Normal Duty Rating (ND)

2 kHz

3 kHz

5A0125

125.0

93.0

5A0145

145.0

108.0

5A0192

192.0

148.0

5A0242

242.0

187.0

u

Temperature Derating

To ensure the maximum performance life, the drive output current must be derated as shown in

Figure A.1

when the drive is

installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. In order to ensure reliable

drive overload protection, set parameters L8-12 and L8-35 according to the installation conditions.

n

Parameter Settings

No.

Name

Description

Range

Def.

L8-12

Ambient

Temperature Setting

Adjust the drive overload (oL2) protection level when the drive is installed

in an environment that exceeds its ambient temperature rating.

-10 to +50

+40 °C

L8-35

Installation Method

Selection

0: IP00/Open-Chassis Enclosure

1: Side-by-Side Mounting

2: IP20/NEMA Type 1 Enclosure

3: Finless Drive or External Heatsink Installation

0 to 3

<1>

<1> Default setting is determined by drive model.

Setting 0: (Models 2A0250 to 2A0415 and 4A0208 to 4A0675)
Setting 2: (Models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242).

Setting 0: IP00/Open-Chassis Enclosure

Drive operation between -10 °C and +50 °C allows 100% continuous current without derating.

Setting 1: Side-by-Side Mounting

Drive operation between -10 °C and +30 °C allows 100% continuous current without derating. Operation between +30 °C and

+50 °C requires output current derating.

Setting 2: IP20/NEMA Type 1 Enclosure

Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and

+50 °C requires output current derating.

Setting 3: External Heatsink Installation, Finless Drive

Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and

+50 °C requires output current derating.

A.4 Drive Derating Data

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

411

A

Specifications

Advertising