A.2 drive specifications – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 406

Advertising
background image

Item

Specification

Protection

Functions

Momentary Power Loss

Ride-Thru

Immediately stop after 15 ms or longer power loss

<6>

.

Continuous operation during power loss than 2 s (standard)

<7>

Heatsink Overheat Protection Thermistor
Braking Resistor Overheat

Protection

Overheat input signal for braking resistor (Optional ERF-type, 3% ED)

Stall Prevention

Stall Prevention is available during acceleration, deceleration, and during run.

Ground Protection

Electronic circuit protection

<8>

DC Bus Charge LED

Remains lit until DC bus voltage falls below 50 V

Environment

Area of Use

Indoors

Ambient Temperature

-10 to +40 °C (IP20/NEMA Type 1 enclosure), -10 to +50 °C (IP00/Open Type enclosure)

Humidity

95 RH% or less (no condensation)

Storage Temperature

-20 to +60 °C (short-term temperature during transportation)

Altitude

Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.

Refer to

Altitude Derating on page 412

for details.

Vibration/Shock

10 to 20 Hz: 9.8 m/s

2

<9>

20 to 55 Hz: 5.9 m/s

2

(2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0099)

2.0 m/s

2

(2A0250 to 2A0415, 4A0208 to 4A1200, and 5A0125 to 5A0242)

Safety Standard

UL 508C (Power Conversion), UL/cUL listed, CSA 22.2 No. 14-05 (Industrial Control Equipment),

CE marked, RoHS compliant, EN 61800-5-1 (LVD), EN 61800-3 (EMC), IEC60529

Protection Design

IP00/Open Type enclosure, IP20/NEMA Type 1 enclosure

<10>

<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors

and with changing motor temperature. Contact Yaskawa for consultation.

<2> Disable Stall Prevention during deceleration (L3-04 = 0) when using a regenerative converter, a regenerative unit, a braking resistor or the Braking

Resistor Unit. The default setting for the Stall Prevention function will interfere with the braking resistor.

<3> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed

down to zero in the shortest time.

<4> Actual specifications may vary depending on motor characteristics.
<5> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<6> May be shorter due to load conditions and motor speed.
<7> A separate Momentary Power Loss Ride-Thru Unit is required for models 2A0004 to 2A0056 and 4A0002 to 4A0031 if the application needs to

continue running for up to 2 seconds during a momentary power loss.

<8> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground

fault is present at the output.

<9> Models 4A0930 and 4A1200 are rated at 5.9 m/s

2

.

<10> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while

maintaining IP20 conformity. This is applicable to models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242.

A.2 Drive Specifications

406

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual