8 main circuit wiring – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 89

Advertising
background image

Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4A0139

R/L1, S/L2, T/L3

3/0

1/0 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

2/0

1/0 to 4/0

⊖, ⊕1

1/0 to 4/0

⊕3

3 to 4/0

4

4

4A0165

R/L1, S/L2, T/L3

4/0

3/0 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

4/0

3/0 to 4/0

⊖, ⊕1

1 to 4/0

⊕3

1/0 to 4/0

4

4 to 2

4A0208

R/L1, S/L2, T/L3

300

2 to 300

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

300

2 to 300

⊖, ⊕1

1 to 250

⊕3

3 to 3/0

4

4 to 300

4A0250

R/L1, S/L2, T/L3

400

1 to 600

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

400

1/0 to 600

⊖, ⊕1

3/0 to 600

⊕3

1 to 325

2

2 to 350

4A0296

R/L1, S/L2, T/L3

500

2/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

500

2/0 to 600

⊖, ⊕1

3/0 to 600

⊕3

1 to 325

M10

18 to 23

(159 to 204)

2

2 to 350

M12

32 to 40

(283 to 354)

4A0362

R/L1, S/L2, T/L3

4/0 × 2P

3/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

4/0 × 2P

3/0 to 600

⊖, ⊕1

4/0 to 600

⊕3

3/0 to 600

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

4A0414

R/L1, S/L2, T/L3

300 × 2P

4/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

300 × 2P

4/0 to 300

⊖, ⊕1

3/0 to 300

⊕3

3/0 to 300

1

1 to 3/0

4A0515

R/L1, S/L2, T/L3

3/0 × 4P

3/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

4/0 × 4P

3/0 to 300

⊖, ⊕1

1/0 to 300

⊕3

1/0 to 300

1/0

1/0 to 300

4A0675

R/L1, S/L2, T/L3

300 × 4P

4/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

300 × 4P

4/0 to 300

⊖, ⊕1

1/0 to 300

⊕3

1/0 to 300

2/0

2/0 to 300

3.8 Main Circuit Wiring

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

89

3

Electrical Installation

Advertising
This manual is related to the following products: