System Configuration Parameters

The EA800 base unit requires certain system level information as outlined in Table 4.

Table 4

System Configuration Parameters

Parameter

Selections

Factory Default

Description

Date Format • MM/DD/YYYY

• DD/MM/YYYY

MM/DD/YYYY

Sets the desired date format for all event time stamps.

Time Format • 12-hour

• 24-hour

24-hour

Sets the desired time format for all event time stamps.

Data Collec-

tion Fre-

quency

• 30 seconds

• 1 minute

• 5 minutes

• 15 minutes

• 30 minutes

• 60 minutes

5 minutes

Sets the interval for collecting and recording data from the

sensors. The data collection frequency applies to all sen-

sors.The EA800 provides approximately 10,000 data

points to be collected regardless of the frequency

selected. The estimated time duration covered for each

data collection frequency is listed below.
30 seconds = 3.5 days
1 minute = 1 week
5 minutes = 1 month
15 minutes = 3 months
30 minutes = 6 months
60 minutes = 1 year

Buzzer

• Enable

• Disable

Enabled

Enables and disables the buzzer when an alarm limit has

been exceeded or a warning condition exists.

WARNING

!

Selecting Disable for this parameter turns the audible

alarm buzzer off completely. No audible alarm tone

will sound when an alarm occurs if DISABLE is

selected.

RF Channel

11 (2405 MHz)
12 (2410 MHz)
13 (2415 MHz)
14 (2420 MHz)
15 (2425 MHz)
16 (2430 MHz)
17 (2435 MHz)
18 (2440 MHz)
19 (2445 MHz)
20 (2450 MHz)
21 (2455 MHz)
22 (2460 MHz)
23 (2465 MHz)
24 (2470 MHz)
25 (2475 MHz)
26 (2480 MHz)

channel 16

Selects the ISM band radio frequency (RF) channel for

transmission between the wireless sensors and EA800

base unit.