Sensor parameter descriptions – Enviro EA800 User Manual

Page 18

Advertising
background image

14

D-011-0152

Sensors

Sensor Parameter Descriptions

This section provides a description of each sensor parameter.

Table 11

Sensor Parameter Descriptions

Parameter

Applicable to Sensors

Description

Sensor Name All

A name used to identify the sensor in the alarm system. Select a name

readily identified by the viewer. The sensor name is displayed on the

Main screen during a no-alarm condition and on the Alarm screen during

an alarm condition. Two name choice types are available:

• Common Name: These are preprogrammed names.

• Custom Name: This selection allows you to enter any name if the

preprogrammed common names do not adequately identify the sensor

in the system (limited to 16 characters).

Note: Duplicate sensor names are not permitted.

Unit of

Measure

• Blue, Red and White

temperature sensors

• 4-20mA sensor

• Wireless

temperature sensors

This parameter allows you to choose the unit of measure used for sen-

sor reading and display.

• Blue, Red and White temperature sensors: °C or °F

• 4-20mA sensors: the following Common Units of measure are

available: F (Fahrenheit), C (Centigrade), K (Kelvin), % rh (percent

relative humidity), psi (pounds per square inch), Pa (Pascals), kPa

(kiloPascals), lb (pound), kg (kilogram)

• 4-20mA sensors can also use custom units. Enter the appropriate units

for the connected 4-20mA sensor via the keypad.

Resolution

4-20mA sensor

This determines the range that may be used for the 4-20mA sensor. The

full scale range is determined by the values entered in the Low Scaled

Value and the High Scaled Value. You must select the correct resolution

in order to set the true range limits for the 4-20mA sensor you are install-

ing. The available values are as follows:

Maximum Allowed

Maximum Allowed

Resolution

Low Scaled Value

High Scaled Value

1.

-9999.

+9999.

0.1

-999.9

+999.9

0.01

-99.99

+99.99

0.001

-9.999

+9.999

Low Scaled

Value

4-20mA sensor

This parameter equals the environmental reading that results in a sensor

output of 4mA or its minimum valid reading. This is dependent on the

setting of the resolution as discussed above.

High Scaled

Value

4-20mA sensor

This parameter equals the environmental reading that results in a sensor

output of 20mA or its maximum valid reading. This is dependent on the

setting of the resolution as discussed above.

Hysteresis

• Blue, Red and White

temperature sensors

• HA-III+

• 4-20mA sensor

The Hysteresis setting helps prevent alarms from being set and reset

continually if the environment is at or near the alarm set point by provid-

ing an acceptable variance. For example, if Hysteresis is set at 2 and the

sensor High limit is set at 50, the sensor reading must decrease to 48

(50 minus 2) in order for the alarm condition to reset to a no-alarm condi-

tion.

Low Alarm

Limit

• Blue, Red and White

temperature sensors

• HA-III+

• 4-20mA sensor

• Wireless humidity

sensor

• Wireless

temperature sensor

The Low Alarm Limit sets the value that trips the low alarm when

exceeded.

Advertising