Accessories – Enviro EA800 User Manual

Page 78

Advertising
background image

74

D-011-0152

Accessories

Accessories

Accessories available for use with the EA800 Environmental Alarm System are listed below.

Wired Water Presence Sensor:

2-wire; maximum 304 m (1000 ft.) cabling length

Wired 4-20mA Sensor

EA800 load (160 Ohms maximum)

Relay Outputs

(9) Form C with 3-terminal NC/COM/NO connections.

Note: There are 8 primary relays (1 dedicated for each sensor) and

1 auxiliary relay.

Relay Contact Ratings

Max 30VDC @ 1 amp resistive.
Not for use with AC power.

Relay Logic

Each relay is user configurable.

Display

128x64 graphic LCD, with blue backlight

Device Environmental Operating Range:

Humidity:

5 to 95% RH, non-condensing

Temperature, Operating:

0°C to 50°C (32° F to 122° F). Not for installation inside coolers or freezers.

Ambient Environmental Quality: Indoor use intended, non-corrosive environment

Conformity Certifications

FCC Part 15, Subpart C, Class B
ICES-003, Issue 3; 1997
NRTL CUE certification mark

Warranty

Two (2) Year Limited Warranty. See Warranty and Service Information.

Notes:
1. Where required, this equipment is to be isolated from the mains supply by a limited power source as specified

in EN60950.
2. All terminals must be connected to a Class 2 Power Limited Circuit complying with the National Electric Code

NFPA 70, Article 725.
3. See “Specifications” on page 46 for power supply requirements.

Table 15

Accessories

Item (Winland Part Number)

Description

BZ-3: Audible alarm module

(PN 1183)

Buzzer for connection to auxiliary relay output that provides audible alarm

indication.

Power supply (transformer)

(PN L-020-0085)

Regulated 110 VAC-to-12 VDC @ >500 mA (minimum) transformer suitable for

use with EA800.

Note: Power supply must be a limited power source per notes 1 and 2 in

Table 14.

Table 14

Specifications — continued

Item

Specification