Specifications

Base Unit and Sensor Specifications

The following table lists the specifications for the EA800 base unit, sensors, and accessories.

Table 14

Specifications

Item

Specification

Dimensions

Approximately 230 mm x 199 mm x 55 mm(“9.375 H x 8.125" W x 2.25" D)

Weight

Base Unit: 0.27 kg (0.6 lb.)
Wireless Sensors: 0.11 kg (0.26 lb.) with batteries

Mounting

The EA800 base unit is mountable directly to 3-gang standard electrical enclo-

sure using pre-drilled holes on the EA800 rear case.
The EA800 base unit and wireless sensors can be mounted to drywall or simi-

lar surfaces using the appropriate anchors (not included).

Case Material

ABS, UL94V-0 rated

EA800 Input (Operating) Volt-

age 1, 2, 3

+11 to +26VDC @

≤500mA current draw. Standard commercial filtered and

regulated power supply suitable. Supplied by AC adapter (not included; see

Accessories) or alarm panel.

Note: Power supply requirement does not include additional require-

ments for loads switched through alarm output relays where

power is derived from EA800 EA400 terminal strip connections.

EA800 Aux Power Out

Equivalent to DC input voltage used: +11 to +26VDC

(Maximum output current 0.5A).

EA800 Real-Time Clock Battery CR2032 (3V Cell)

Wireless Sensor Input Voltage

Either:

• +12VDC @ <100mA current draw using a 2.1 mm barrel plug, center

positive; OR

• 2xAA Alkaline Batteries (1.5V Cell)

Wireless Sensor Radiating

Power (minimum, at PCB

antenna connector)

• EA800 base unit: -3.5 dBm

• Sensors: -2.5 dBm

Wireless Sensitivity:

(minimum at printed circuit

board antenna connection)

• EA800: -94.5 dBm

• Sensors: -95.5 dBm

Low and High Limit Adjust Range:

(Winland thermistor sensors only)

Temperature: -80° C to 150° C

(-112° F to 302° F)

Note: The Low and High Limit Adjust Range is dependent upon the

sensor being used. See “Accessories” on page 44.

Humidity: 5 to 95% RH

Note: The Low and High Limit Adjust Range is dependent upon the

sensor being used. See “Accessories” on page 44.

Water Presence: No Alarm / Alarm

Sensors

Up to four wired sensors
Up to four wireless sensors

Cable Length to Wireless

Multi-Function Sensor

EA-WMFS

100 ft. maximum

Wired Temperature Sensor:

2-wire; maximum 304 m (1000 ft.) cabling length

Wired Humidity Sensor:

3-wire; maximum 304 m (1000 ft.) cabling length