Enviro EA800 User Manual

Page 28

Advertising
background image

24

D-011-0152

Connecting Wired Temperature, Contact Closure, and Water Bug Sensors

Note:

It may take a few minutes for the base unit to detect the wireless sensors.

At this point the

NEW WIRELESS SENSOR screen is displayed and an arrow moves from left to right indicating that the

EA800 is waiting to receive sensor ID data. When the EA800 has communicated with the reachable sensors the

SELECT SENSOR screen displays a list of wireless sensors detected.

When a sensor is detected, confirm that the ID
number shown matches the ID number on the
sensor’s label..

If the sensors can communicate with the EA800,
their IDs appear in the list as shown in the
example at right. Do not permanently install the
sensors that appear in the list until you verify
their signal strength when you program the
wireless sensors in the system later in the
installation process.

If the list of number(s) on the screen does not

contain the number found on the sensor's PC

board, press F1 (CANCEL) to continue the

search process.

Note:

Press the Reset Button on the sensor to

restart the search process if necessary.

After the base unit has identified each wireless sensor and you have programmed it, temporarily mount it in its

desired location using tape. This allows the sensor to be relocated if necessary in order to obtain good signal

strength

Connecting Wired Temperature, Contact Closure, and Water Bug Sensors

1.

Make certain the sensor's wiring is passed through the opening in the mounting plate.

2.

Remove the adapter from the correct input connector header by pulling the adapter up and off of the circuit

board header connector.

3.

Strip the ends of each of the sensor's wires as indicated by the gauge on adapter you just removed.

4.

Insert the stripped wire ends into screw terminals of the adapter as indicated by the EA800 Wiring Diagram you

completed in the preparation phase. There is no need to observe polarity when connecting sensor wires. See

Figure 14.

Figure 14 EA800 Base Unit Wired Temperature, Contact Closure, and Water Bug Sensor Connections

5.

Secure the connections using the setscrews on the adapter. Check the connection by lightly pulling on each

connection.

6.

After connecting the wire ends to the adapter, align the adapter to the correct header pins as indicated by your

EA800 Wiring Diagram, and press the adapter fully onto the header connector pins.

RESET BUTTON

SENSOR MODEL NO.

(Example: EA-WTS = Wireless Temperature Sensor)

MAC Address Label

Figure 13 Wireless Sensor IDs and MAC Address Location