1. Flue pipe must be as large as the flue collar on the draft

diverter.

2. Maintain an upward slope of at least 1/4 inch (6mm) per

foot of horizontal run.

3. Run flue pipe as directly as possible with a minimum of

elbows.

4. Flue pipe should extend through the wall of a chimney

to be flush with inner wall.

5. Flue pipe must be adequately supported by metal

straps.

6. Single wall vent pipe may be attached directly to the draft

hood of the fireplace heater when a clearance of 2 1/2 inches

(64mm) is maintained between the single wall vent pipe and

the combustible wall of the room in which the fireplace heater

is located. Use double wall vent pipe for clearances less than

2 1/2 inches (64mm) to combustibles.

7. For flue pipe running through walls and roof, use B-1 [1

inch (25mm) clearance to combustibles] vent pipe.

8. Chimneys should extend at least 2 feet (.6m) above the

roof and above any object or nearby building within 10 feet

(3m).

9. Open tees should not be used in the flue pipe.

10. Appliance must not be connected to a chimney flue that is

servicing a separate solid-fuel burning appliance.

For proper venting, do not attach a 90° elbow directly to draft

diverter. If possible, attach 2 feet (.6m) of straight vent pipe before

an elbow is used. Use of 45° elbows is recommended.
Uninsulated single-wall metal pipe shall not be used outdoors

in cold climates for venting gas utilization equipment.
Ventilation and Combustion Air

Fireplace heaters shall be installed in a location in which the

facilities for ventilation permit satisfactory combustion of gas

and proper venting under normal conditions. In buildings of

conventional frame, brick or stone construction without tight storm

windows and doors, infiltration is normally adequate to provide

for combustion and draft hood dilution.
Where appliances are installed in a confined space within a

building, the building being of unusually tight construction, air for

combustion and ventilation must be obtained directly from outdoors

or from such spaces that freely communicate with the outdoors.

Under these conditions, the confined space shall be provided with

two permanent openings, one near the top of the enclosure and one

near the bottom; each opening shall have a free area of not less

than one square inch (6.5cm

2

) per 1,000 BTU's (.3KW) of total

input. The draft hood must be in the same atmospheric pressure

zone as the combustion air inlet to the appliance and shall be so

located so that the relief opening is accessible for checking vent

operation.
Liner and Insulated Liner

When you install a vented fireplace heater into a masonry chimney

you must follow these steps.

1. The chimney must be lined and sized properly. Most masonry

chimneys are over sized and absorb too much heat to be

considered a proper vent. If you have any doubts line the

chimney with the right size liner. If it's unlined you must line

it.

2. Use an insulated liner when the chimney is on the outside,

three sides exposed to the weather, and there is no clay liner

in the chimney. The insulation will help keep the flue gases

warmer.

Insulated Vent Enclosure (Figure 15)

Vented fireplace heaters installed with the vent going directly to

the outside and above the eaves can cause poor venting. The cold

pipe will have a delay in proper venting and cause the fireplace

heater to shut "off" by the vent safety switch. To prevent delayed

venting as well as condensation of flue products an insulated

enclosure is recommended.
Use type B 4" (102mm) diameter vent pipe and maintain at least

a one inch (25mm) clearance to combustibles.
Use metal thimble to protect vent pipe as it passes through

combustibles

.

Figure 15

VENTING