Thermo Pride Air Handler MA User Manual

Page 15

Advertising
background image

15

* Optional dehumidification humidistat switch contacts open on humidity rise.

Notes:

1. “Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.

2. Move HUM STAT Jumper on AH Control Board to YES position if Humidistat is used.

3. MODE Jumper on AH control board should be set to A/C for air conditioners.

* Optional dehumidification humidistat switch contacts open on rise.

Notes:

1. “Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.

2. Move HUM STAT Jumper on AH Control Board to YES position if Humidistat is used.

3. MODE Jumper on AH control board should be set to HP for heat pumps.

4. To change quantity of heat during HP defrost cycle - Reverse connections at W1 & W2 on Air Handler Control Board.

SECTION X: MAINTENANCE

Filters must be cleaned or replaced when they become dirty. Inspect at

least once per month. The frequency of cleaning depends upon the

hours of operation and the local atmospheric conditions. Clean filters

keep unit efficiency high.

LUBRICATION

The bearings of the blower motor are permanently lubricated.

FIGURE 11: Cooling Models with Electric Heat Wiring

MA SERIES - Air Handler Control Wiring

Typical A/C - Cooling only Applications

THERMOSTAT

AIR HANDLER

BOARD

1 - STAGE

AIR CONDITIONING

R

R

G

Y

W1

W2

C

G

W1

W2

Y

C

Y / Y2

Y1

O

HUM

X / L

COM

HUMIDISTAT *

THERMOSTAT

AIR HANDLER

BOARD

1 - STAGE

AIR CONDITIONING

R

R

G

Y

W1

W2

C

G

W1

W2

Y

C

Y / Y2

Y1

O

HUM

X / L

COM

HUMIDISTAT *

MA SERIES - Air Handler Control Wiring

Typical A/C with Electric Heat Applications

FIGURE 12: Single-Stage Cooling Wiring

THERMOSTAT

AIR HANDLER

BOARD

HEAT PUMP

R

R

R

G

G

Y

W / W1

O

W

O

O

C

X / L

X / L

C

Y / Y2

Y1

Y

W1 66

W2

W1

HUM

COM

HUMIDISTAT

*

W2

E

X / L

And Newer UPG Single Stage HP Systems

CONTROL WIRING - AHP or MA Series Air Handler

Single Stage H/P with Standard Demand Defrost Control Board

Advertising