Notice – Thermo Pride Air Handler MA User Manual

Page 21

Advertising
background image

5

AIR FILTERS

Air filters and filter racks must be field supplied.

.

SUSPENSION KITS

A suspension kit is available. Models 1BH0601 (unit size 018-060) is

designed specifically for the units contained in this instruction (upflow

application only). For installation of these accessory kits, see the

instructions packed with the kit.

HORIZONTAL SUSPENSION

For suspension of these units in horizontal applications, it is recom-

mended to use angle steel support brackets with threaded rods, sup-

porting the units from the bottom, at the locations shown in Figure 4.

SECTION IV: ELECTRIC HEATER

INSTALLATION

If the air handler requires electric heat, install the electric heat kit

according to the installation instructions included with the kit. After

installing the kit, mark the air handler nameplate to designate the heater

kit that was installed. If no heater is installed, mark the name plate

appropriately to indicate that no heat kit is installed.
The HEAT ENABLE jumper (See Figure 5) must be moved to the HEAT

position to enable operation of the heater

Use only 4HK heater kits, as listed on Air Handler name plate and in

these Instructions. Use data from Tables 9 and 12 for information on

required minimum motor speed tap to be used for heating operation,

maximum over-current protection device required and minimum electri-

cal supply wiring size required for listed combination of Air Handler and

Heater Kit.
For Upflow, Downflow and Horizontal right hand applications the kits

can be installed without modification.
Field modification is required for Horizontal left-hand airflow application

only. Follow instructions with heater for modification.

SECTION V: LOW VOLTAGE CONTROL

CONNECTIONS

This air handler can be connected to the wall thermostat and outdoor A/

C or heat pump using either conventional low voltage (24 VAC) thermo-

stat wiring OR using four-wire digital communications wiring. To use

conventional low voltage wiring, see the section below entitled “Con-

ventional Low Voltage Control Wiring”. To use four-wire communica-

tions control wiring, see the section below entitled “Control Wiring using

Communicating Controls”.
The Communicating System consists of several intelligent communicat-

ing components including the Communicating Thermostat Control

(touch-screen wall thermostat), variable speed air handler, air condi-

tioner (15 and 18 SEER premium air conditioners) or heat pump (13, 15

and 18 SEER premium heat pumps), which continually communicate

with each other via a four-wire connection called the A-R-C-B. Com-

mands, operating conditions, and other data are passed continually

between components over the A-R-C-B bus. See Figure 8. The result is

a new level of comfort, versatility, and simplicity.
In order to use this air handler in full communications (COMM) mode, it

MUST be installed with the matching touch-screen Communicating

Control (wall thermostat) and an outdoor air conditioner or heat pump

with a fully communicating control.
This air handler may also be used along with the Communicating Ther-

mostat Control and a non-communicating outdoor air conditioner

through the addition of a communicating Outdoor Aux Control board to

the outdoor unit. This system allows full communication between the air

handler and thermostat and limited communication to the outdoor unit.

Equipment should never be operated without filters.

Units

(Nominal Tons)

Dimension

WW

XX

YY

1-1/2 - 3 Ton

16”

48”

22”

3-1/2 - 5 Ton

24”

53” - 58”

22”

FIGURE 5: Typical Horizontal Installation

WW

XX

SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL APPLICATIONS

2

1-1/2

MIN. 1-1/2” x 1-1/2” Angle

Recommended length

26” minimum

with 2” clearance on

both sides of Air Handler

MIN. 3/8”

THREADED ROD

YY

If a heat kit with a circuit breaker is installed in the air handler, the
circuit breaker cover cladding must be removed to gain access to
the sheet metal cover plate. Some local codes may require that the
circuit breaker remain visible. If so, do not re-install circuit breaker
cover cladding.

NOTICE

Advertising
This manual is related to the following products: