13

* May be 0 (no breaker) or 1 (with breaker).

2. Heaters are 3 Phase.

TABLE 11: Electrical Data - (For Single Source Power Supply) - Copper Wire 1 Ø - 208/230-1-60

Models

MV

Heater

Models*

Heater

Amps

240V

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

Amps/Type

1

75°C Wire Size - AWG

208V

230V

208V

230V

208V

230V

12B

4HK*6500506

20.0

27.54

30.38

30

35

10

8

4HK*6500806

31.3

39.73

44.50

40

45

8

8

4HK*6501006

40.0

49.21

55.38

50

60

8

6

4HK16501306

54.2

64.00

72.80

70

80

4

2

4HK165N1506

60.0

70.88

80.38

90

90

4

3

12D

4HK*6500506

20.0

27.54

30.38

30

35

10

8

4HK*6500806

31.3

39.73

44.50

40

45

8

8

4HK*6501006

40.0

49.21

55.38

50

60

8

6

4HK16501306

54.2

64.00

72.80

70

80

4

2

4HK16501506

60.0

70.88

80.38

90

90

4

3

4HK16501806

73.3

85.32

97.00

90

100

4

3

4HK16502006

80.0

92.54

105.38

100

125

3

1

16C

4HK*6500506

20.0

29.29

31.88

30

35

10

8

4HK*6500806

31.3

41.48

46.00

45

50

8

8

4HK*6501006

40.0

50.96

56.88

60

60

6

6

4HK16501306

54.2

66.40

75.20

70

80

4

2

4HK16501506

60.0

72.63

81.88

90

90

3

3

4HK16501806

73.3

87.07

98.50

90

100

3

2

4HK16502006

80.0

94.29

106.88

100

125

3

1

20D

4HK*6500506

20.0

29.29

31.88

30

35

10

8

4HK*6500806

31.3

41.48

46.00

45

50

8

8

4HK*6501006

40.0

53.08

58.75

60

60

6

6

4HK16501306

54.2

68.40

77.20

70

80

4

2

4HK16501506

60.0

74.75

83.75

90

90

3

3

4HK16501806

73.3

89.19

100.38

90

110

3

2

4HK16502006

80.0

96.42

108.75

100

125

3

1

4HK16502506

100.0

118.08

133.75

125

150

1

1/0

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

TABLE 12: Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/230-3-60

Models

Heat Kit -

Three Phase

Heater

Amps

240V

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

1

Amps/Type

75°C Wire Size - AWG

208V

230V

208V

230V

208V

230V

12B

4HK06501025

23.1

30.9

34.3

35

35

8

8

12D

4HK06501025

23.1

30.9

34.3

35

35

8

8

4HK06501525

34.7

43.4

48.8

45

50

8

8

4HK06501825

41.4

50.6

57.1

50

60

8

6

16C

4HK06501025

23.1

32.6

35.1

35

35

8

8

4HK06501525

34.7

45.1

49.6

45

50

8

8

4HK06501825

41.4

52.4

58.0

60

60

6

6

20D

4HK06501025

23.1

34.8

37.6

35

40

8

8

4HK06501525

34.7

47.3

52.1

50

60

8

6

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.