TABLE 13: Electrical Data - (For Multi-Source Power Supply) - Copper Wire 1 Ø - 208/230-1-60

Models

MV

Heater

Models

Min. Circuit Ampacity

Max. O.C.P.

Amps/Type

1

75°C Wire Size - AWG

Circuit

Circuit

Circuit

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

208/230

208/230

208/230

208/230 208/230 208/230 208/230 208/230 208/230

12B

4HK16501306

41.7/47.9

22.4/25.0

50/50

30/30

6/6

12/10

4HK165N1506

49.2/55.4

21.7 / 25.0

50/60

25/25

8 / 6

10/10

12D

4HK16501306

41.7/47.9

22.4/25.0

50/50

30/30

6/6

12/10

4HK16501506

49.2/55.4

21.7/25.0

50/60

25/25

8 / 6

10/10

4HK16501806

45.6/51.2

39.7/45.8

50/60

40/50

8 / 6

8/8

4HK16502006

49.2/55.4

43.3/50.0

50/60

45/50

8 / 6

8/8

16C

4HK16501306

42.9/49.1

23.6/26.2

50/50

30/30

6/6

12/10

4HK16501506

51.0/56.9

21.7/25.0

50/60

25/25

8 / 6

10/10

4HK16501806

17.3/52.7

39.7/45.8

50/60

40/50

8 / 6

8/8

4HK16502006

51.0/56.9

43.3/50.0

50/60

45/50

8 / 6

8/8

20D

4HK16501306

43.9/50.1

24.6/27.2

50/60

30/30

6/6

10/10

4HK16501506

53.1/58.8

21.7/25.0

60/60

25/25

6 / 6

10/10

4HK16501806

49.5/54.6

39.7/45.8

50/60

40/50

8 / 6

8/8

4HK16502006

53.1/58.8

43.3/50.0

60/60

45/50

6 / 6

8/8

4HK16502506

49.3/56.5

43.3/50.0

21.7/25.0

50/60

45/50

25/25

8 / 6

8/8

10/10

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

TABLE 14: Electrical Data - (For Multi-Source Power Supply) - Copper Wire - 208/230-3-60

Models

Heater

Model

Minimum Circuit Ampacity

Max. O.C.P.

1

Amps/Type

75°C Wire Size - AWG

Circuit

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

20D

4HK16502525

41.0/44.9

31.3/36.1

45/45

35/40

8/8

8/8

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.