Figure 23

Single Flue - Vertical Vent Run

with 45 degree elbows

VENT EXAMPLES FOR SINGLE FLUE (cont.)

Figure 22

Minimum Exterior Grade Dimension - Single Flue, Horizontal Venting Below Floor

WARNING: Major U.S. building codes specify minimum chimney and/or vent height above the rooftop. These minimum heights are

necessary in the interest of safety. These specifications are summarized in Figure 23.

MANTEL

PVC PIPE

(SUPPLIED BY INSTALLER)

2 - 45 DEG. PVC

BENDS (SUPPLIED

BY INSTALLER)

GAS SUPPLY

FLASHING

H

SURROUND

MODEL #PVE-1

VENT CAP

(SUPPLIED WITH VENT KIT)

MODEL #PVVK-SV

FLEXIBLE PVC PIPE

WITH 1/2” COUPLING ON EACH END

MODEL #PVVK-CFA

X

12

ROOF PITCH

IS

12

X

ROOF PITCH

H (Min.)

Flat to 6/12

12” (305 mm)

6/12 to 7/12

15” (381 mm)

Over 7/12 to 8/12

18” (457 mm)

Over 8/12 to 16/12

24” (610 mm)

Over 16/12 to 21/12

36” (914 mm)

Determining Minimum Vent Height Above

the Roof