Vertical examples for colinear direct vent – Empire Comfort Systems PV-28SV50-B User Manual

Page 25

Advertising
background image

24820-1-0409

Page 25

VERTICAL EXAMPLES FOR COLINEAR DIRECT VENT

Figure 28

Calculation example of vent run maximum 40’

Determining Minimum Vent Height Above the Roof
WARNING:
Major U.S. building codes specify minimum chimney and/or vent height above the rooftop. These minimum heights are

necessary in the interest of safety.

Special Note: The vent terminal (PTrap, Vent cap or two 90° elbows) and first 90° elbow off back of the heater, when within 6”

(15.2 cm) off back of the heater, do not contribute to the overall vent length measurement. For each 45° elbow installed in the

horizontal run, the length of the horizontal run MUST be reduced by 1.5 feet (45 cm). This does not apply if the 45° elbows are

installed on the vertical part of the vent system. Reduce the length of the horizontal run 3 feet (91.4 cm) for every 90° elbow.
Note:
Exhaust must be a minimum of 3”

above air intake inlet.

Advertising
This manual is related to the following products: