Introduction

4

1.1.3 Split Systems

Each air-cooled split system consists of an evaporator section and one of the following condensing

units.

Prop Fan Air-Cooled

Prop Fan units include scroll compressor, condenser coil, prop fan, high pressure switch, hot gas

bypass and Liebert Lee-Temp head pressure control. Unit is designed for outdoor location.

Centrifugal Fan Air-Cooled

Centrifugal Fan units include scroll compressor, condenser coil, centrifugal blower assembly,

high-pressure switch, hot gas bypass and Liebert Lee-Temp head pressure control. Unit must be

mounted indoors. Duct flanges are optional.

Water-Cooled

Each water-cooled split system consists of an evaporator section and a water/glycol condensing unit,

which includes scroll compressor, coaxial condenser, water regulating valve, hot gas bypass and

high-pressure switch. Design pressure is 150 psi (1034 kPa) as standard and 350 psi (2413 kPa) as

optional.

Glycol-Cooled

Each glycol-cooled split system consists of an evaporator section, a water/glycol condensing unit (as

described above), a pump package, and a 95°F (35°C) design ambient drycooler.