Installation (Applicable to all Models)

9

2.5

Piping Considerations

All piping below the elevated floor must be located so that it offers the least resistance to air flow.

Careful planning of the piping layout under the raised floor is required to prevent the air flow from

being blocked. When installing piping on the subfloor, it is recommended that the pipes be mounted in

a horizontal plane rather than stacked one above the other. Whenever possible, the pipes should be

run parallel to the air flow.
Condensate pumps for downflow units are shipped separately to be field-installed under the raised

floor. Pump height is 11 inches (279 mm).

2.5.1 Drain Line

A 3/4" (19.1 mm) female pipe thread (FPT) connection is provided for the evaporator coil condensate

drain. This drain line also drains the humidifier, if applicable. The drain line must be located so it will

not be exposed to freezing temperatures. The drain should be at least the full size of the drain connec-

tion and pitched a minimum of 1/8" per ft. (11 mm per meter).

NOTE
This line may contain boiling water. Select appropriate drain system materials.
The drain line must include one and only one trap. Units without a condensate pump have a

factory-supplied trap in the unit, so a field trap should not be added. Units with a condensate

pump will require a field-supplied trap downstream from the pump. The drain line must

comply with all applicable codes.

Table 2

Piping connection size

Air-Cooled Unit Connection Sizes—in.

Model No. BF/BU

(50 Hz)

Liquid Line O.D. Copper

L

Hot Gas Line OD Copper

HG

042A (040A)

3/8

5/8

067A (065A)

1/2

7/8

Split System Fan Coil Unit Connection Sizes—in.

Model No. BF/BU (50 Hz)

Liquid Line

L

Suction Line

SC

036E (035E)

5/8 - 18 Female (#6 QC)

1-1/8 - 12 Female (#11 QC)

060E (059E)

1/2 OD Cu

1-1/8 OD Cu

All Units: Connection Sizes—in.

Humidifier Line

OD Copper

H

Condensate

Drain Line

C

Condensate Pump Line

OD Copper

P

Hot Water Reheat

OD Copper

1/4

3/4 FPT

1/2

Supply

HWS

Return

HWR

5/8

5/8

Water/Glycol-Cooled Unit Connection Sizes—inches

Model No. BF/BU

(50 Hz)

Supply Line

S

Return Line

R

046WG (045WG)

7/8

7/8

071WG (070WG)

1-1/8

1-1/8

GLYCOOL Unit Connection Sizes —in.

Model No. BE/BK

(50 Hz)

Supply Line

S

Return Line

R

061G (058G)

1-1/8

1-1/8

Chilled Water Unit Connection Sizes—in.

Model No. BF/BU

(50 Hz)

Supply Line

CWS

Return Line

CWR

068C (072C)

1-1/8

1-1/8

102C (101C)

1-1/8

1-1/8