Installation (Applicable to all Models)

16

Figure 10 Piping connections for chilled water self-contained units - Downflow models

PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)

Condensate Drain
3/4" FPT
Field pitch a minimum
of 1/8" (3.2mm) per ft. (305mm).
The drain line must comply
with all applicable codes.

Humidifier Water Supply Line
1/4" OD CU

Chilled Water Return Line
1-1/8" OD CU

Hot Water Return
5/8" OD CU (optional)

Chilled Water Supply Line
1-1/8" OD CU

Hot Water Supply
5/8" OD CU (optional)

DPN000371
Rev. 01

Liebert iCOM
Control