Air-Cooled Models—Self-Contained Compressor

26

3.4

Fan Speed Control Systems

The Variable Fan Speed Control systems (FSC & VFD) uses pressure-activated electronic fan speed

control systems and remotely located thermostat(s) to ensure operation at ambient temperatures as

low as 0°F (-18°C). For this ambient temperature range, the VFD Control Condenser must be used

with digital scroll indoor units and can be used for energy savings with any Liebert Challenger 3000

unit.

Variable Fan Speed Control Piping

A discharge line and a liquid line must be field-installed between the indoor unit and the outdoor con-

denser. See Figures 15 and 16 for details.

Table 6

Equivalent lengths (feet) for various pipe fittings

Copper Pipe

O.D. in.

90 Degree

Elbow Copper

90 Degree

Elbow Cast

45 Degree

Elbow

Tee

Gate

Valve

Globe

Valve

Angle

Valve

1/2

0.8

1.3

0.4

2.5

0.26

7.0

4.0

5/8

0.9

1.4

0.5

2.5

0.28

9.5

5.0

3/4

1.0

1.5

0.6

2.5

0.3

12.0

6.5

7/8

1.45

1.8

0.8

3.6

0.36

17.2

9.5

1-1/8

1.85

2.2

1.0

4.6

0.48

22.5

12.0

1-3/8

2.4

2.9

1.3

6.4

0.65

32.0

16.0

1-5/8

2.9

3.5

1.6

7.2

0.72

36.0

19.5

Refrigerant trap = 4 times equivalent length of pipe per this table.

Table 7

Indoor unit refrigerant charge lb (kg)

Model

R407C

Approximate Charge

lb (kg)

42A/40A

0.9 (0.4)

67A/65A

1.4 (0.6)

Table 8

Line charges - refrigerant per 100 ft. (30 m) of Type “L” copper tube

O.D.

R407C

Liquid Line

lb (kg)

Hot Gas Line

lb (kg)

1/2"

7.3 (3.3)

1.3 (0.6)

5/8"

11.7 (5.3)

2.1 (1.0)

3/4"

16.6 (7.5)

3.0 (1.4)

7/8"

24.4 (11.1)

4.4 (2.0)

Table 9

Condenser refrigerant (per serial tag)

Model

R407C

Approximate Charge

lb (kg)

Fan Speed

Liebert

Lee-Temp*

083

8 (3)

25 (12)

104

9 (4)

37 (17)

165

15 (6.8)

50 (22.7)

* Charge includes the receiver charge.