Figure 24 pump packages—expansion tank, Table 17 mounting hole dimensional data, Table 18 drycooler data – Emerson 3000 User Manual

Page 54: Table 19 glycol pump data, Table 17, Mounting hole dimensional data, Table 18, Drycooler data, Table 19, Glycol pump data

Advertising
background image

Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor

48

Figure 24 Pump packages—expansion tank

Table 17

Mounting hole dimensional data

PUMP PACKAGE

A

in (mm)

B

in (mm)

C

in (mm)

SINGLE (0.75 - 7.5 Hp)

15-1/4 (387.4)

2-1/2 (63.5)

22-1/2 (571.5)

DUAL (0.75 - 5 Hp)

30-1/4 (768.4)

2-1/2 (63.5)

22-1/2 (571.5)

Table 18

Drycooler data

Model

No.

No. of

Fans

Weight

lb (kg)

Drycooler

Conn. Sizes

(Suct. & Disc.) in.

“A” Dimension

in. (mm)

“B” Dimension

in. (mm)

“C” Dimension

in. (mm)

Coil Internal

Volume gal. (l)

-069

1

410 (186)

1-1/4

51-1/2 (1308)

44 (1118)

42 (1067)

2.4 (9.2)

-092 1 430

(195)

1-1/2

51-1/2

(1308)

44 (1118)

42 (1067)

3.7 (13.9)

-109

1

450 (204)

2

51-1/2 (1308)

44 (1118)

42 (1067)

4.9 (18.6)

-112

1

470 (213)

2

51-1/2 (1308)

44 (1118)

42 (1067)

5.8 (22.0)

-139

2

565 (256)

2

91-1/2 (2324)

84 (2134)

82 (2083)

4.8 (18.2)

-197

2

605 (274)

2

91-1/2 (2324)

84 (2134)

82 (2083)

9.0 (34.1)

Table 19

Glycol pump data*

Pump

Pump Suction

Connection in.

Pump Discharge

Connection in.

Hp

Hz

3/4

60

1-1/4

3/4

1-1/2

60

1-1/4

3/4

2

60

1-1/4

3/4

3

60

1-1/2

1

5

60

1-1/2

1-1/4

3/4

50

1-1/4

3/4

1

50

1-1/4

3/4

1-1/2

50

1-1/4

3/4

2

50

1-1/4

3/4

3

50

1-1/2

1-1/4

* Connection sizes apply to primary pump supplier

1/2" FPT

Fitting

1/2" FPT

Fitting

6-13/16"

(173mm)

17-1/4"

(438.2mm)

30-1/2

(774.7mm)

4"

(101.6mm)

2-3/4"

(69.9mm)

SL-10065 Pg. 7B
SL-10070 Pg. 6B

O 9"

(228.6mm)

O 1/2" (12.7mm) 8 holes

EXPANSION TANK

8.8 gal. (33.3L)

1-1/2"

(38.1mm)

1-1/2" (38.1mm)

1" (25.4mm)

1"

(25.4mm)

6-1/8"

(155.6mm)

7"

(177.8mm)

3"

(76.2mm)

2-1/2"

(63.5mm)

Advertising