Installation (Applicable to all Models)

14

Figure 8

Piping connections for water/glycol and GLYCOOL units - Downflow models

DPN000364
Rev. 01

Condensate Drain
3/4" FPT
Field pitch a minimum
of 1/8" (3.2mm) per ft. (305mm).
The drain line must comply with
all applicable codes

Humidifier Water Supply Line
1/4" OD CU

Condenser Return Line
7/8" OD CU on Models BF046WG/BF045WG
1-1/8" OD CU on Models BF071WG/BF070WG

Hot Water Return
5/8" OD CU (optional)

Condenser Supply Line
7/8" OD CU on Models BF046WG/BF045WG
1-1/8" OD CU on Models BF071WG/BF070WG

Hot Water Supply
5/8" OD CU (optional)

PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)

iCOM Control
Panel