Air-Cooled Models—Self-Contained Compressor

33

Figure 17 General arrangement—Air-cooled models with Liebert Lee-Temp

* Components are not supplied by Liebert
but are recommended for proper
circuit operation and maintenance.
* * Components supplied by Liebert
and must be field installed.

FACTORY PIPING

FIELD PIPING

Piping Assembly * *

Condenser Coil

Rotalock Valve * *

1/4" ( 6.4mm)
Pressure Relief
Valve * *

Sight Glass

Liebert
Lee-Temp
Receiver

Head Pressure
Control with
Integral Check
Valve

Check
Valve

Evaporator Coil

Sensing Bulb

Expansion
Valve

Hot Gas
Bypass
Valve

Hot Gas
Bypass

Solenoid
Valves

Sight Glass

Filter Dryer

Shutoff
Valve *

Liquid Return

External
Equalizers

Service
Valves

Scroll
Compressor

Liquid Return
from Condenser

Traps * Every
25 Ft. (7.6m)
of rise on Hot
Gas Line only

Inverted Trap * on
discharge line to
extend above base
of coil by a minimum
of 7-1/2" (190mm)

OPTIONAL PIPING

Hot Gas Discharge

Check Valve

DPN000674
Rev. 02