Split System Models

68

Figure 37 3-ton centrifugal air-cooled condensing unit (con't.)

DPN000207
Rev0

Single- or three-phase
electric service
not by Liebert

Optional factory-installed
disconnect switch

Factory-wired
to components
on electric panel

Line voltage electric power
supply conduit entrance

Field-supplied 24V
NEC Class 2 wiring
to fan/coil unit

Single- or three-phase
electric service
not by Liebert

Field-supplied unit disconnect
switch when optional disconnect
is not provided in unit

Connection terminal
for field-supplied
grounding wire

Low-voltage electric
power supply entrance

Heat rejection connection.
Field-supplied 24V NEC
Class 2 wiring. See NOTE 2.

NOTES:

1. Refer to specification sheet for full load amp. and wire size amp. ratings.

2. Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75' (23m)

or not to exceed 1 volt drop in control line.

Wire connections from evaporator

mod:

1. 24V ground

2. 24V supply

3. High-pressure alarm (optional)

4. Hot gas bypass connection

(only on units with hot gas

bypass)